E44-467 · Filter Clogging and Contamination · Fuel Filter 30μm · ★★
At -20C fuel waxes out and ices up, the screen plugs solid, fuel supply is interrupted, and the engine stalls
[Mechanism] Low temperature causes wax/water to freeze and plug the pores.
[Calculation] At -20°C wax precipitation shrinks the effective pore size by 70%, v=Q/A rises 3x, Δp suddenly exceeds the limit, and flow cuts off.
[Design Omission] No heating, no dehydration, and no anti-freeze additive, so icing occurred.
1) Add a pre-filter heater to hold temperature >5°C against waxing; since at -20°C wax precipitated, pores shrank 70%, and flow cut off, heating prevents plugging;
2) Add a dehydrator to keep water <200ppm; since water freezes and plugs the pores, dehydration removes it;
3) Add an anti-freeze additive to the fuel to lower the pour point; since congealing causes plugging, the additive prevents it;
4) Heat-trace and insulate the filter housing; since cold causes congealing, heat tracing keeps it warm;
5) Add a low fuel-supply pressure alarm; since plugging drops the pressure, the alarm gives warning;
6) Choose a wide-channel screen to resist wax binding; since narrow passages bind, the wide channel avoids it;
7) Preheat and circulate before low-temperature start-up; since cold causes plugging, preheating prevents it;
8) Write anti-freeze measures into the low-temperature procedure; since the lack of protection was the root cause of the icing, the procedure provides the check.
GB/T 26114-2010 Filters for liquid filtration