Knowledge Base › Fluid Systems Error Case › Circulating-Water Side-Stream Filter Excessive Backwash Water Use

Circulating-Water Side-Stream Filter Excessive Backwash Water Use

E44-478 · Filter Clogging and Contamination · Circulating-Water Side-Stream Filter 200t/h · ★★

Problem Description

Backwash used 30t per cycle, 2% of the system; water consumption was high, and make-up water could not keep up, lowering the water level

Root Cause

[Mechanism] Backwash intensity was too high and drainage time too long.
[Calculation] Backwash intensity q=15L/s·m² exceeded the required 8; per-cycle water use = qt = 30t, 2% of the circulation rate.
[Design Omission] Backwash intensity and duration were not optimized, and there was no water reuse, so water use was excessive.

Corrective Solution

1) Reduce backwash intensity to 8L/s·m² and halve the duration; since 15 exceeded the need and used 30t (2%), lower intensity saves water;
2) Settle and reuse backwash water; since the clarified water can be recycled, reuse conserves it;
3) Backwash automatically based on turbidity; since timed backwashing was too frequent, turbidity-based control adjusts it;
4) Add a water-use metering alarm; since high consumption should be visible, metering monitors it;
5) Optimize the media gradation to reduce plugging; since plugging causes frequent backwashing, better gradation reduces it;
6) Stagger backwash of the two tanks; since simultaneous backwashing competes for water, staggering avoids it;
7) Use online outlet water quality to control backwash frequency; since stable quality needs less washing, quality-based control reduces it;
8) Write backwash water use into the operating procedure; since excessive intensity was the root cause, the operating procedure provides the check.

Checklist

Reference

GB/T 26114-2010 Filters for liquid filtration