E44-480 · Filter Clogging and Contamination · Lube-Filter Differential-Pressure Switch · ★★
The differential-pressure switch falsely tripped at 0.2MPa and shut the machine down, while actual Δp was only 0.05, causing a false shutdown and line interruption
[Mechanism] The switch diaphragm fatigued and the setpoint drifted.
[Calculation] The setpoint drifted to 0.05 and the switch actuated; false-trip rate reached 30%, while actual Δp was only 0.05.
[Design Omission] The setpoint was not calibrated and no dual-switch verification was used, so false trips occurred.
1) Reset and calibrate the switch to 0.2MPa; since it had drifted to 0.05 and tripped the line, recalibration prevents false trips;
2) Use two switches in series for voting; since a single switch trips easily, dual voting improves reliability;
3) Set a 3-month calibration interval; since drift develops gradually, scheduled calibration catches it;
4) Compare against the actual Δp gauge; since the gauge provides evidence, comparison verifies the switch;
5) Replace the switch with a solid-state pressure transmitter; since mechanical switches drift, a transmitter avoids it;
6) Trace false-trip records; since frequent trips indicate a problem, records support root-cause analysis;
7) Add a time-delay confirmation to suppress chattering; since chatter causes false trips, the delay filters it out;
8) Write setpoint calibration into the instrument-calibration procedure; since the switch was never calibrated, the root cause of drift, the calibration procedure provides the check.