E44-498 · Filter Blockage and Fouling · Pure-Water RO Cartridge Filter 5μm · ★★
Security filter fouled, RO inlet pressure drops, permeate output drops, membrane fouled
[Mechanism] High SDI of the pretreatment effluent fouls the cartridge.
[Calculation] SDI=5 exceeds 3, fouling rate rises, Δp=0.3MPa, RO inlet pressure drops.
[Design Omission] SDI not controlled and cartridges not replaced frequently; fouling results.
1) Control pretreatment SDI <3, because the original SDI of 5, rising fouling rate and Δp=0.3 caused the blockage, so SDI control prevents fouling;
2) Replace the cartridge filter based on Δp, because over-limit lowers output, so replacement is scheduled;
3) Add scale inhibitor to the feed, because scaling blocks it, so scale inhibition is used;
4) Monitor RO inlet pressure, because blockage drops it, so monitoring is provided;
5) Upsize cartridge capacity one grade, because low capacity means short life, so larger capacity is used;
6) Flush pretreatment equipment regularly, because buildup blocks it, so scheduled flushing is used;
7) Online effluent water quality, because fouling degrades it, so online monitoring is used;
8) Write SDI control and cartridge replacement into the RO specification, because the lack of control was the root cause of fouling, so the RO spec governs.
GB/T 26114-2010 Liquid filters - Filters for filtration