E44-071 · Heat-Exchanger Fouling and Insufficient Heat Transfer · Seawater Condenser · ★★
Marine growth and silt attachment cut the overall heat-transfer coefficient K by 18%, raise the terminal difference by 5℃, and drop unit vacuum by 3kPa.
[Fouling] Marine growth on the tube wall adds fouling resistance R=δ/λ, which accounts for a share of the total thermal resistance.
[Calculation] The fouling layer cuts overall K by 18%, raises the terminal difference Δt by 5℃, and drops the vacuum.
[Design Omission] No chlorination or biocidal dosing was provided and no periodic cleaning was scheduled; fouling reduced performance.
1) Provide chlorination or electrolytic biocidal treatment to prevent attachment, since marine life needs conditions to survive and biocide suppresses attachment, thus keeping walls clean and K from dropping;
2) Provide continuous sponge-ball cleaning (ball recovery ≥95%), since balls travel with the flow and scrub the tube walls, physically removing fouling, thus holding K at the design value;
3) Raise the flow velocity to ≥1.5m/s to prevent deposition, since low velocity lets marine growth and silt settle while high velocity scours, thus reducing attachment;
4) Provide inlet filtration and antifouling (bar screen + biocide), since cutting fouling at source reduces clogging, thus lowering the cleaning load;
5) Monitor terminal-difference and vacuum trends, since a 5℃ terminal-difference rise and 3kPa vacuum drop are fouling signatures and the trend gives warning, thus cleaning early;
6) Periodically clean tubes with high-pressure water, since attachment is tenacious and scheduled mechanical cleaning ensures K, thus restoring heat transfer;
7) On commissioning, measure K up to the design value; heat exchange is the core function and must be measured, giving acceptance;
8) Make biocidal treatment a mandatory seawater-design item, since the original absence of biocide caused fouling, so a biocide system must be laid out at the design stage.
GB/T 151-2014 Heat exchangers