Seawater Condenser Marine Growth Fouling Reduces Heat Transfer

E44-071 · Heat-Exchanger Fouling and Insufficient Heat Transfer · Seawater Condenser · ★★

Problem Description

Marine growth and silt attachment cut the overall heat-transfer coefficient K by 18%, raise the terminal difference by 5℃, and drop unit vacuum by 3kPa.

Root Cause

[Fouling] Marine growth on the tube wall adds fouling resistance R=δ/λ, which accounts for a share of the total thermal resistance.
[Calculation] The fouling layer cuts overall K by 18%, raises the terminal difference Δt by 5℃, and drops the vacuum.
[Design Omission] No chlorination or biocidal dosing was provided and no periodic cleaning was scheduled; fouling reduced performance.

Corrective Solution

1) Provide chlorination or electrolytic biocidal treatment to prevent attachment, since marine life needs conditions to survive and biocide suppresses attachment, thus keeping walls clean and K from dropping;
2) Provide continuous sponge-ball cleaning (ball recovery ≥95%), since balls travel with the flow and scrub the tube walls, physically removing fouling, thus holding K at the design value;
3) Raise the flow velocity to ≥1.5m/s to prevent deposition, since low velocity lets marine growth and silt settle while high velocity scours, thus reducing attachment;
4) Provide inlet filtration and antifouling (bar screen + biocide), since cutting fouling at source reduces clogging, thus lowering the cleaning load;
5) Monitor terminal-difference and vacuum trends, since a 5℃ terminal-difference rise and 3kPa vacuum drop are fouling signatures and the trend gives warning, thus cleaning early;
6) Periodically clean tubes with high-pressure water, since attachment is tenacious and scheduled mechanical cleaning ensures K, thus restoring heat transfer;
7) On commissioning, measure K up to the design value; heat exchange is the core function and must be measured, giving acceptance;
8) Make biocidal treatment a mandatory seawater-design item, since the original absence of biocide caused fouling, so a biocide system must be laid out at the design stage.

Checklist

Reference

GB/T 151-2014 Heat exchangers

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »