E44-073 · Heat-Exchanger Fouling and Insufficient Heat Transfer · Double-Pipe Heat Exchanger (Crude Oil) · ★★
Oil temperature below the wax-appearance point causes wax to precipitate and adhere to the wall, cutting K by 22%; insufficient heat-transfer temperature drop leaves outlet oil temperature 5℃ low.
[Wax Deposition] Oil temperature below the wax-appearance point causes wax to precipitate and adhere to the wall, adding fouling resistance.
[Calculation] A 0.8mm wax layer cuts K by 22%, leaving the temperature drop insufficient.
[Design Omission] Oil temperature was not held above the wax-appearance point and wax was not removed; wax deposition caused the drop.
1) Hold oil temperature above the wax-appearance point (e.g., ≥45℃), since below it wax precipitates and adheres to the wall and holding temperature prevents precipitation, thus keeping K up and heat transfer sufficient;
2) Provide hot-oil online cleaning to remove wax (periodic backflush), since hot oil dissolves deposited wax and restores a clean wall, thus bringing K back up;
3) Add external pipe insulation to reduce wall-temperature drop, since insulation keeps near-wall oil above the wax-appearance point and prevents wax precipitation, thus maintaining heat transfer;
4) Monitor wall temperature to prevent waxing (alarm if wall temp > wax-appearance point), since wall temperature is the direct criterion for waxing and monitoring gives warning, thus raising temperature in time;
5) Periodically remove wax mechanically (tube scraping), since a 0.8mm wax layer needs mechanical removal and scraping restores the bore, thus preserving flow area and K;
6) Fit temperature-difference measurement points (inlet/outlet Δt), since insufficient temperature drop is a result of waxing and measuring Δt back-calculates K, thus verifying it;
7) On commissioning, measure K up to the design value; heat exchange is the core function and must be measured, giving acceptance;
8) Bring oil-temperature control into crude design, since the original lack of temperature control caused waxing, so temperature control must be laid out at the design stage.
GB/T 151-2014 Heat exchangers