E44-124 · Heat-Exchanger Fouling and Insufficient Heat Transfer · Plate Heat Exchanger · ★★
Cooling-water hardness of 300mg/L causes fouling; K drops from 3500 to 1800W/m²K, and outlet temperature runs high.
[Fouling] CaCO3 precipitates as scale, adding thermal resistance.
[Calculation] A 0.5mm scale layer cuts K by 40%.
[Design Omission] No softening or cleaning was provided, leading to insufficiency.
1) Soften the cooling water to hardness ≤50mg/L, since this reduces CaCO3 precipitation, thus lessening fouling;
2) Provide continuous sponge-ball cleaning, since it physically removes scale, thus preserving K;
3) Control velocity ≥1.5m/s to prevent deposition, since high v keeps scale from adhering, thus reducing it;
4) Add corrosion-inhibiting antiscalant, since it suppresses precipitation, thus extending cleaning intervals;
5) Monitor terminal-difference and K trends, since a K drop signals fouling, thus handling it early;
6) Periodically chemically clean, since accumulated scale must be removed, thus restoring K;
7) Measure K to design value on test run, since design requires verification, thus confirming delivery;
8) Bring water treatment into heat-exchanger design, since hard water was the main cause, thus fixing it to prevent recurrence.
GB/T 151-2014 Heat exchangers