E44-125 · Heat-Exchanger Fouling and Insufficient Heat Transfer · Steam Condenser · ★★
Noncondensables occupy 5% of the shell side, K drops, condensing load is insufficient, and vacuum falls.
[Noncondensable Gas] The gas film adds thermal resistance.
[Calculation] 5% noncondensables cut K by 25%.
[Design Omission] No continuous air extraction was provided, leading to insufficiency.
1) Provide a high-efficiency ejector to continuously remove noncondensables, since the gas film adds thermal resistance, thus raising K;
2) Fit vent valves at shell-side high points, since gas collects at the top, thus venting easily;
3) Hold steam quality ≥0.98, since wet steam carries gas, thus reducing gas;
4) Monitor vacuum and K, since a drop signals gas, thus extracting early;
5) Periodically check airtightness to prevent in-leakage, since external leakage adds gas, thus sealing;
6) Provide extraction-vapor condensation recovery, since it saves energy, thus improving efficiency;
7) Measure vacuum and K to design values on test run, since design requires verification, thus confirming delivery;
8) Bring air extraction into condenser design, since missed extraction was the main cause, thus fixing it to prevent recurrence.
GB/T 151-2014 Heat exchangers