E44-126 · Heat-Exchanger Fouling and Insufficient Heat Transfer · Shell-and-Tube Heat Exchanger Bypass · ★★
A bypass valve leaks 30% internally, sending medium on a short circuit; effective heat-transfer flow drops and outlet does not meet spec.
[Short Circuit] A bypass leak sends part of the medium around the tube bundle.
[Calculation] A 30% short circuit cuts effective Q, and outlet temperature fails to meet spec.
[Design Omission] The bypass was not tightly closed and no check valve was fitted, causing a short circuit.
1) Specify a zero-leakage globe valve for the bypass and close it tightly, since internal leakage causes a short circuit, thus sealing it;
2) Fit a check valve on the bypass to prevent backflow, since it prevents cross-flow, thus making it one-way;
3) After closing, verify no leakage (no temperature rise across the bypass), since this reveals leakage, thus confirming;
4) Reduce the bypass line size to ≤10% of the main line, since a smaller line leaks less, thus limiting the short circuit;
5) Monitor outlet temperature in operation, since an abnormal temperature signals a short circuit, thus catching it early;
6) Periodically inspect valve-seat sealing, since internal leakage requires repair, thus maintaining it;
7) On test run verify outlet temperature to design and no bypass flow, since design requires verification, thus confirming delivery;
8) Bring bypass management into heat-exchanger operation, since a leaking short circuit was the main cause, thus fixing it to prevent recurrence.
GB/T 151-2014 Heat exchangers