E44-506 · Heat-Exchanger Fouling and Insufficient Heat Transfer · Plate Heat Exchanger (316) · ★★
Plates foul, pressure differential rises, flow drops, and heat transfer is insufficient.
[Mechanism] Scale jams the narrow gaps between plates.
[Calculation] A 2mm gap lets scale occupy 30%, raises v, gives Δp=0.2MPa, and lowers K.
[Design Omission] No backflushing was provided and water was hard, causing scale clogging.
1) Disassemble and clean plates to remove scale (quarterly high-pressure rinse / chemical wash), since a 2mm narrow gap with 30% scale, Δp=0.2MPa, and reduced flow requires it, thus restoring gaps and flow paths by disassembly cleaning;
2) Soften inlet water (hardness ≤60mg/L), since hard-water Ca/Mg jams scale in narrow gaps that cannot be cleaned thoroughly, thus softening to suppress hard scale;
3) Provide differential-pressure alarm (alarm at Δp>0.2MPa), since fouling raises the pressure differential before flow visibly drops, thus warning early of the clogging trend;
4) Schedule backflushing (weekly; force-flush at Δp>0.15MPa), since accumulated scale reduces flow area and raises pressure differential, thus backflushing on schedule to remove scale;
5) Choose a wide-gap plate pattern (corrugation gap ≥3mm), since narrow gaps jam scale and cannot be cleaned thoroughly, thus wide gaps aid flushing and prevent jamming;
6) Raise velocity to prevent settling (≥1.2m/s), since scale settles and adheres in low-velocity zones and jams with time, thus raising velocity to cut residence time and suppress settling;
7) Dose dispersant (antiscalant dosed as required), since crystal nuclei adhere to the wall and dispersion suppresses crystallization, thus dispersing to inhibit scale;
8) Write disassembly cleaning and softening into the plate-exchanger procedure, since the original design omitted cleaning and softening, the root cause of fouling, thus controlling by procedure.
GB/T 16409-2018 Plate heat exchangers