E44-526 · Heat Exchanger Fouling and Insufficient Heat Transfer · Hydraulic Oil Cooler Air-Cooled · ★★
Air-side dust plugs the fins, K drop, high oil temperature
[Mechanism] Dust coats the fins and blocks airflow.
[Calculation] Dust lowers α, cuts K by 30%, and pushes oil temperature 10℃ over limit.
[Design Omission] No filtration and no flushing, so dust blocks the unit.
1) Filter inlet air and flush the fins to restore α; dust on the fins blocks airflow (lower α, K drop 30%, oil temp +10℃ over limit), so filtering and flushing restore K;
2) Schedule flushing (each shift / dust season); dust builds and hardens, so periodic flushing keeps it clear;
3) Oil-temperature alarm (on exceeding setpoint); dust blockage raises oil temperature with a risk, so the alarm prevents over-temperature;
4) Widen fin spacing (≥5 mm); tight spacing lets dust bridge and block airflow, so wider gaps reduce plugging;
5) Suppress ambient dust (enclosure / spray); less dust slows deposition and lengthens cleaning intervals;
6) Use a VFD fan to modulate airflow; oil temperature follows airflow, so modulating it compensates and stabilizes temperature;
7) Inspect fins on schedule (visual / Δp); dust builds and resistance rises, so inspection guides flushing;
8) Write filtration and flushing into the liquid-cooling procedure; the original design omitted filtration and flushing, the root cause of dust, so the procedure closes the loop.
GB/T 151-2014 Heat exchangers