E44-1070 · Heat Exchanger Fouling and Insufficient Heat Transfer · Heat Exchanger · ★★
Hard water, fouling, efficiency drop
[Mechanism] High circulating-water hardness causes water scale to precipitate on the heated surfaces; scale adheres to the tube wall, lowering K and causing insufficient heat transfer.
[Calculation] Hardness 450 mg/L (as CaCO3), scale thickness 2 mm/year, K drops by 35%, outlet temperature 7℃ low.
[Design Omission] No water softening, no scale inhibitor, and no hardness control were provided.
1) Soften the water (ion exchange to hardness≤50 mg/L); because hardness causes fouling and softening slows it, this suppresses fouling;
2) Verify inlet hardness≤150 mg/L (actual 450); because high hardness causes fouling and hardness verification ensures it, this suppresses fouling;
3) Add a scale inhibitor (dose periodically); because fouling causes scale and inhibition slows it, this suppresses fouling;
4) Stabilize and raise flow velocity (v≥1.2 m/s); because low velocity causes fouling and raising it slows it, this suppresses fouling;
5) Perform a heat-transfer test (measure K and temperature rise); because fouling was never verified and direct measurement confirms efficiency, this determines efficiency from data;
6) Install hardness + temperature-difference monitoring (alarm on overshoot); because fouling first shows up as a temperature drop, this monitors fouling and gives early warning;
7) Control blowdown in operation (concentration ratio≤3); because concentration causes fouling and blowdown control slows it, this prevents fouling during operation;
8) Write water softening and scale inhibition into the specification; because the root cause of hard-water fouling is the lack of softening and hardness control, the specification enforces control.
GB/T 151-2014 Heat exchangers