E44-1069 · Heat Exchanger Fouling and Insufficient Heat Transfer · Heat Exchanger · ★★
Bypass leaks, short circuit, efficiency drop
[Mechanism] A large bypass gap inside the heat exchanger lets part of the fluid short-circuit around the tube bundle, reducing heat transfer.
[Calculation] Bypass gap 5 mm, bypass flow accounts for 25%, effective heat-transfer flow only 75%, outlet temperature 6℃ low.
[Design Omission] No bypass sealing, no seal verification, and no sealing plate were provided.
1) Seal the bypass gap (add a seal strip / sealing plate); because leakage causes short-circuiting and sealing restores efficiency, this raises efficiency;
2) Verify the seal gap≤1 mm (actual 5); because leakage causes short-circuiting and tight sealing ensures it, this prevents short-circuiting;
3) Add a sealing plate (separate the passes); because cross-flow causes short-circuiting and a plate separates it, this restores flow;
4) Replace the gasket (full contact); because an old gasket causes short-circuiting and a new gasket seals tightly, this seals the joint;
5) Perform a heat-transfer test (verify outlet temperature reaches design); because short-circuiting was never verified and direct measurement confirms efficiency, this determines efficiency from data;
6) Install inlet/outlet temperature-difference monitoring (alarm on temperature drop); because short-circuiting first shows up as a temperature drop, this monitors efficiency and gives early warning;
7) Control assembly quality in operation (ensure tight seal contact); because poor assembly causes short-circuiting and assembly control seals it, this prevents short-circuiting during operation;
8) Write bypass sealing and gap verification into the assembly card; because the root cause of bypass short-circuiting is the lack of sealing and gap verification, assembly enforces control.
GB/T 151-2014 Heat exchangers