Knowledge Base › Fluid Systems Error Case › Non-Condensable Gas Accumulation Poor Heat Transfer

Non-Condensable Gas Accumulation Poor Heat Transfer

E44-1068 · Heat Exchanger Fouling and Insufficient Heat Transfer · Heat Exchanger · ★★

Problem Description

Non-condensable gas accumulates, poor efficiency, temperature rise

Root Cause

[Mechanism] Non-condensable gas accumulates inside the heat exchanger, forming a gas film on the tube wall that sharply increases thermal resistance and reduces heat transfer.
[Calculation] Non-condensable gas occupies 8% of the shell side; gas-film resistance drops K by 30%, outlet temperature is 10℃ low, and vacuum drops.
[Design Omission] No vent, no vent-position verification, and no non-condensable gas removal were provided.

Corrective Solution

1) Add a high-point vent (automatically removes non-condensable gas); because gas occupancy causes poor efficiency and venting restores it, this raises efficiency;
2) Verify vent position (at the highest point); because a low position causes accumulation and a high position vents it, this prevents accumulation;
3) Add a periodic vent valve (vent each shift); because accumulation causes poor efficiency and venting restores it, this restores efficiency;
4) Stabilize and raise flow velocity (disrupts the gas film); because low velocity causes accumulation and higher velocity disperses it, this suppresses accumulation;
5) Perform a heat-transfer test (measure K and temperature rise); because poor efficiency was never verified and direct measurement confirms it, this determines efficiency from data;
6) Install non-condensable gas monitoring (alarm on vacuum drop); because gas first shows up as a vacuum drop, this monitors gas and gives early warning;
7) Control venting in operation (vent periodically); because long intervals cause accumulation and scheduled venting removes it, this prevents accumulation during operation;
8) Write venting and high-point positioning into the calculation sheet; because the root cause of non-condensable gas accumulation is the lack of venting and a low vent position, the calculation enforces control.

Checklist

Reference

GB/T 151-2014 Heat exchangers