E44-028 · Uneven Flow Distribution · Multi-branch cooling water pipe · ★★
Three parallel branches with a flow ratio 45:30:25 out of balance, branch 2 overheats and alarms, temperature difference 12℃
[Impedance] Different pipe lengths/diameters between the branches make the impedance ratio ≠1, and the flow ∝1/√R.
[Flow Imbalance] The low-resistance branch fights for flow and the high-resistance branch is starved and overheats.
[Design Omission] No hydraulic balancing calculation and no balancing valves were provided, so the flow deviation causes the overheating.
1) Size each branch pipe by a hydraulic balance calculation, because an impedance ratio ≠1 makes the flow ∝1/√R and causes flow deviation and overheating (branch 2, 12℃ temperature difference), thereby calculating the resistance and sizing the diameters;
2) Fit a balancing valve on each branch to adjust the flow, because the valve allows on-site opening adjustment to balance the R of each branch, thereby splitting the flow as required;
3) Add restrictor orifices when the resistance difference is large, because the orifices fix the restriction and prevent flow fighting, thereby hard-limiting the flow;
4) Lay out the branches with equal length and equal diameter, because equal impedance balances the flow naturally, thereby evening the layout;
5) Measure the flow of each branch and adjust it to the design ratio, because only measurement confirms the balance, thereby balancing by data;
6) Install temperature measuring points to monitor the flow deviation, because branch overheating and temperature difference signal the deviation, thereby giving a temperature warning;
7) Verify at commissioning that the flow ratio is balanced, because a balanced flow means no local overheating, thereby performing acceptance;
8) Build the balancing calculation into the piping-network design, because the missing balancing calculation was the root cause of the flow deviation, so the design must include it.
GB/T 20801-2020 Pressure piping code