E44-181 · Uneven Flow Distribution · Orifice plate flowmeter · ★★
The orifice plate was installed backwards with the sharp edge facing downstream, the flow reading is 18% low and the pressure loss increased
[Reverse Installation] The sharp edge of the orifice plate must face the flow; reversed, it disturbs the flow pattern.
[Undersized] Reverse installation raises the pressure loss and the reading is low.
[Design Omission] The plate was not installed per the marking and the orientation was not checked, so the reading is low.
1) Install the orifice plate with the sharp edge facing the flow, because reverse installation reads 18% low and increases the pressure loss, thereby installing it in the flow direction;
2) Check the flow-direction marking before installation, because a mistake reverses it, thereby checking the marking;
3) Mark a permanent flow direction on the valve body, because without a mark it is easily reversed, thereby marking the direction;
4) Verify at commissioning that the flow reading matches the actual flow, because the design requires measurement, thereby confirming delivery;
5) Keep ≥10D of straight pipe upstream and downstream to preserve the flow pattern, because a short run disturbs it, thereby lengthening the straight run;
6) Train installers to recognize the orientation, because human error causes reverse installation, thereby providing training;
7) Set up a flow-direction inspection step, because a missed check reverses the plate, thereby establishing the step;
8) Build the orientation check into the installation, because the missing check was the root cause of the reverse installation, so the installation must include it.
GB/T 2624-2016 Orifice-plate flowmeters