E44-730 · Uneven Flow Distribution · Tube bundle · ★★
Bundle deviation, efficiency loss
[Mechanism] A tube-bundle flow deviation lowers the efficiency.
[Calculation] The deviation lowers the efficiency by 15%.
[Design Omission] No distribution, no verification, and no inspection were provided, so the feed distribution is wrong.
1) Provide an inlet distributor (bell mouth + guide vanes, uniform distribution), because the original bundle deviation made the pass flows differ by >20% and lowered the heat-transfer efficiency by 15%, thereby distributing and evening the flow;
2) Verify the resistance of each pass (pressure drop of each pass, difference ≤5%), because a difference causes deviation and verification evens it, thereby verifying the resistances;
3) Standardize the tube diameter against deviation (same diameter on each pass, deviation ≤2%), because a diameter difference causes deviation and standardization evens it, thereby standardizing the diameters;
4) Monitor the flow deviation (outlet temperature of each pass, alarm above a 3℃ difference), because gradual deviation is invisible and monitoring catches it, thereby giving early warning;
5) Even out the pass division (accurate pass partition plate, equal splitting), because a difference causes deviation and control evens it, thereby evening the passes;
6) Run a heat-balance test (temperature difference of each pass, accept when even), because the lack of testing caused the deviation and testing verifies it, thereby testing the balance;
7) Clean the tubes against blockage-induced deviation (clean at fixed intervals, remove scale), because blockage causes deviation and cleaning restores flow, thereby cleaning the tubes;
8) Write the distribution and resistance verification into the specification (distribution uniformity), because the missing distribution was the root cause of the bundle deviation and freezing it into the specification enforces control.
GB/T 151-2014 Heat exchangers