E44-746 · Uneven Flow Distribution · Distribution header · ★★
Low pressure at the far end, low flow
[Mechanism] Low pressure at the far end reduces the flow.
[Calculation] The pressure drop makes the far-end flow low.
[Design Omission] No diameter increase, no verification, and no inspection were provided, so the far-end pressure drops.
1) Increase the far-end diameter of the header (one size larger than the front end, drop ≤5% of the total), because the original far-end low pressure left the far-end flow at only 60% of the front end, thereby increasing the diameter to cut the drop;
2) Verify the header pressure drop (calculate along the run, compensate at the far end), because the drop makes the far-end flow low and verification evens it, thereby verifying the drop;
3) Add far-end pressure boosting (far-end pump, pressure make-up), because low pressure makes the flow small and boosting restores it, thereby boosting the pressure;
4) Even out the branch resistances (same resistance in each branch, difference ≤3%), because unequal resistance makes the flow small and evening it out balances the flow, thereby balancing the resistances;
5) Monitor the far-end pressure (fit a gauge at the far end, alarm on low pressure), because a gradual drop is invisible and monitoring catches it, thereby giving early warning;
6) Run a flow test (measure each branch, accept when even), because the lack of testing caused the low flow and testing verifies it, thereby testing the flow;
7) Keep the total flow steady (steady pump), because changing conditions make the flow low and control steadies it, thereby steadying the total flow;
8) Write the diameter increase and drop verification into the calculation sheet (header pressure-drop profile), because the missing diameter increase was the root cause and freezing it into the calculation sheet enforces control.
GB/T 20801.3-2020 Design code for industrial metallic piping