E44-755 · Uneven Flow Distribution · Averaging Control · ★★
The two loops interfere with each other, flow fluctuates ±15%, level biased >8%
[Mechanism] The two coupled loops were not tuned.
[Calculation] Without decoupling, the flow fluctuates ±15%, the level is biased >8%, and the decay ratio is <0.6.
[Design Omission] The controllers were not tuned to the loop characteristics and not tested, so the control was out of adjustment.
1) Tune each loop's PID to its own time constant (main loop Kp=0.8/Ti=12s, secondary loop Kp=1.6/Ti=6s), because the omitted tuning let the two loops couple, making the flow fluctuate ±15% and the level be biased >8%, thereby decoupling and holding the fluctuation to ±3% with the loops working in step;
2) Set the setpoint ramp to ≤5%/min, because the original step setpoint made the secondary loop overshoot >20% and the main loop unable to follow, thereby cutting the overshoot by ramping and keeping the loops in step;
3) Run a joint two-loop step test (apply a 10% step and record the response curve), because the omitted joint test left the tuning blind and the decay ratio below <0.6 with oscillation, thereby finding the best parameters and bringing the decay ratio to 0.75~0.9;
4) Set each loop's gain to its own characteristics (lower the large-capacity loop's Kp by 30%, raise the small-capacity loop's Kp by 20%), because using one gain for both made the large loop sluggish and the small loop oscillate, thereby matching characteristics and making the responses consistent;
5) Add a deviation alarm (alarm above 5%), because the missing alarm let the deviation grow to ±12% before it was noticed, thereby catching it early and keeping it from accumulating;
6) Limit the loop output's rate of change to ≤8%/s, because the abrupt output made the valve stroke repeatedly and the flow chatter, thereby steadying the valve and smoothing the flow;
7) Retune every quarter and run a step check, because long-term neglect let the parameters drift and the deviation grow, thereby keeping the loop stable by periodic re-verification;
8) Write the tuning parameters and ramp slope into the control card and lock it, because the omitted tuning let O&M change parameters freely and was the root cause, thereby keeping the parameters correct.
GB/T 17214 Industrial-process measurement and control