E44-756 · Uneven Flow Distribution · Split-Range Control · ★★
Gap at the switch point, flow gap >8%, control lost
[Mechanism] The split range has no overlap, leaving a gap.
[Calculation] No overlap at the switch point creates a flow gap >8% at the 50% signal and makes the controlled variable jump.
[Design Omission] No overlap band was set and the switch points were not verified, so a gap remained.
1) Set the split-range overlap band (±5% signal overlap, both valves open between 46% and 54%), because the missing overlap at the switch point closed one valve and opened the other with a gap as the signal passed 50%, leaving a flow gap >8%, thereby eliminating the dead zone and making the handover continuous;
2) Verify the valve switch points (main valve closes at 52%, secondary opens at 48%, giving 4% overlap), because mismatched switch points closed or opened both valves together and lost control, thereby re-verifying for a seamless handover;
3) Run a full-range split test (sweep the signal 0-100% and record both valves' opening curves), because the omitted test left the overlap blind and the gap undiscovered, thereby proving continuity by the swept curve;
4) Check the switching state (record the valve positions at the switch point, alarm if both close), because gradual bias erases the overlap and reintroduces the gap, thereby monitoring the handover online;
5) Select equal-percentage valves (match both valves' flow characteristics and gain handover), because a large characteristic mismatch steps the gain at the handover and makes the control chatter, thereby evening the handover by matching the characteristics;
6) Verify the gain handover (total gain continuous at the switch point), because a mismatch overshoots at the gap, thereby steadying the transition by gain verification;
7) Periodically check the split range (sweep the signal and verify the overlap every quarter), because gradual bias shrinks the overlap and the gap returns, thereby keeping continuity by periodic re-verification;
8) Write the overlap band and switch points into the control card, because the missing overlap was the root cause of the gap, thereby keeping the handover seamless.
GB/T 17214 Industrial-process measurement and control