E44-757 · Uneven Flow Distribution · Selective Control · ★★
Wrong control selected, controlled variable over limit, protection failed
[Mechanism] The selector logic picks the wrong channel.
[Calculation] Wrong logic fails to switch when it should and pushes the controlled variable >10% past the safe limit.
[Design Omission] The logic was not verified and not tested, so the wrong channel was selected.
1) Verify the selector type (MIN for high-pressure selection / MAX for low-pressure selection; wiring it backwards causes misoperation), because the reversed selection cut over when protection should engage and pushed the controlled variable >10% past the limit, thereby re-verifying the direction against the protection intent;
2) Set switching conditions and deadband (switching differential ≥2% against chatter), because the missing deadband made the two controllers switch back and forth at the boundary and the output chatter, thereby steadying the selection with deadband;
3) Test the selection logic (simulate both inputs going over limit and verify the right channel is selected), because the omitted test left the logic error hidden and the wrong channel selected, thereby proving the correct switching sequence by test;
4) Verify the output limit against misoperation (output limiting ±5%), because a wrong selection makes the output jump and shocks the equipment, thereby cushioning the shock by limiting;
5) Monitor the selection state (display which controller is active, alarm on switching), because blind selection hides misoperation and the over-limit grows, thereby monitoring the state;
6) Show the state for confirmation (display the active source on the operator panel), because hiding it invites misjudgment and wrong O&M changes, thereby preventing error by showing the state;
7) Periodically check the logic (verify the selection conditions every quarter), because parameter drift changes the conditions and reintroduces the wrong selection, thereby reviewing regularly;
8) Write the selection logic and deadband into the control card, because the omitted verification was the root cause of the wrong selection, thereby keeping the selection correct.
GB/T 17214 Industrial-process measurement and control