Imbalance in a Variable-Flow System

E44-766 · Uneven Flow Distribution · Variable-Flow System · ★★

Problem Description

As the load varied, each loop's flow deviated >20% and some were starved

Root Cause

[Mechanism] The pipe network is not dynamically balanced under variable flow.
[Calculation] A load change shifts the original balance point and biases each loop's flow >20%.
[Design Omission] The variation was not controlled and the network was not rebalanced, so an imbalance occurred.

Corrective Solution

1) Provide variable-flow balance control (adjust the pump frequency with the load, with balance valves following), because under the original variable load the fixed balance point shifted and biased each loop >20%, thereby controlling the variation and evening the flow;
2) Rebalance the network (compute a balance opening for each of the maximum and minimum conditions), because the resistance changes with the flow and a single-point balance is not enough, thereby rebalancing for both conditions;
3) Calibrate each loop's flow (measure each loop's flow under variable load), because a difference biases the flow and calibration reveals it, thereby tuning it accurately by measurement;
4) Provide differential-pressure control (control the supply-return differential pressure to ±0.02MPa), because off-design conditions let the differential pressure drift and control steadies it, thereby preserving the flow by controlling the pressure;
5) Monitor the deviation (monitor each loop's flow, alarm above 15% deviation), because the deviation grows gradually and starves some loops and monitoring gives early warning, thereby monitoring the deviation;
6) Run a variable-load test (simulate 50%/100% load and record each loop's flow), because the omitted test let the off-design deviation go unnoticed, thereby proving even distribution in every condition;
7) Control the total flow (change the total flow smoothly with the load), because a sudden change breaks the balance and steadiness preserves it, thereby steadying the total;
8) Write the variation control and rebalancing into the control card, because the omitted control was the root cause of the variation problem and the control card enforces it, keeping the variable flow even.