E44-765 · Uneven Flow Distribution · Differential-Pressure Controller · ★★
Differential pressure fluctuated >±0.02MPa and the controlled variable was unsteady
[Mechanism] The differential-pressure setpoint or tuning is wrong.
[Calculation] Poor tuning makes the differential pressure fluctuate >±0.02MPa with a decay ratio <0.6.
[Design Omission] The controller was not tuned and the sensor was not calibrated, so it was out of adjustment.
1) Retune the differential-pressure setpoint (set the value from the process surplus pressure, PID Kp=1.2/Ti=8s), because the original mistuning made the differential pressure fluctuate >±0.02MPa and the system hunt, thereby restoring steady pressure by tuning;
2) Calibrate the sensor accurately (actual calibration of the Δp zero/span ±0.5%), because a deviation causes wrong control and an inaccurate measurement keeps the control inaccurate, thereby restoring accuracy by calibrating the transmitter;
3) Run a differential-pressure closed-loop comparison test (apply a disturbance and record the response curve), because the omitted test left the tuning blind and oscillating, thereby finding the best parameters by test;
4) Adjust the gain for stability (lower the gain against integral windup), because oscillation biases the pressure and lowering the gain steadies it, thereby steadying the loop by adjusting the gain;
5) Monitor the deviation (monitor the differential pressure, alarm above ±0.015MPa fluctuation), because gradual deviation makes the system hunt and early detection helps, thereby monitoring the deviation;
6) Limit the rate of change (output ≤5%/s against abrupt valve motion), because an abrupt change biases the pressure and rate limiting steadies it, thereby steadying by limiting the rate;
7) Check the differential pressure at intervals (recalibrate the sensor and tuning every quarter), because gradual drift reintroduces the bias and periodic recalibration corrects it, thereby keeping the pressure steady;
8) Write the tuning and transmitter calibration into the control card, because the omitted tuning was the root cause of the pressure problem and the control card enforces it, keeping the differential pressure steady.
GB/T 17214 Industrial-process measurement and control