E44-764 · Uneven Flow Distribution · Balance Valve · ★★
Balance valves fully open, each loop's flow biased >20%
[Mechanism] The balance valve was not adjusted to the calculated opening.
[Calculation] Being fully open lets the low-resistance loop rob flow while the high-resistance loop is biased >20%.
[Design Omission] The valve was not adjusted and its position was not marked, so it was not adjusted.
1) Adjust the balance valve to the calculated opening (use a special wrench to set it until the flow is on target, then lock it), because the original fully open valve let the low-resistance loop rob flow and biased the high-resistance loop >20%, thereby distributing the flow evenly by adjusting the valve;
2) Calibrate each valve's flow (measure each loop's actual flow and compare with the design), because a difference biases the flow and calibration reveals it, thereby tuning it accurately by measurement;
3) Mark the valve positions (mark the opening after locking to prevent tampering), because blind adjustment lets O&M casually open them wider and reintroduces the bias, thereby preventing tampering by marking positions;
4) Run a hydraulic balance test (commission the whole system and record each loop's flow), because the omitted test let the bias go unnoticed and the operation ran abnormally, thereby proving even distribution;
5) Check the setting (monitor each valve position, alarm on drift), because gradual deviation re-disorders the flow and early detection helps, thereby monitoring the adjustment;
6) Control the total pressure (keep the total pressure steady against balance-point jumps), because off-design conditions defeat the adjusted valves and steadiness preserves them, thereby stabilizing the pressure;
7) Inspect the balance at intervals (remeasure each loop's flow every quarter), because gradual deviation causes long-term inaccuracy and renewed disorder, thereby recalibrating periodically;
8) Write the valve adjustment and flow calibration into the maintenance card, because the omitted adjustment was the root cause and the maintenance card enforces it, keeping the valves always adjusted.
GB/T 20801.3-2020 Design code for industrial metallic piping