Knowledge Base › Fluid Systems Error Case › Excessive Flow in the Near-End Loop

Excessive Flow in the Near-End Loop

E44-763 · Uneven Flow Distribution · Near-End Loop · ★★

Problem Description

Near-end flow exceeded >120% of design, far end starved

Root Cause

[Mechanism] The near-end loop has low resistance and robs the flow.
[Calculation] The low near-end resistance pushes its flow above >120% and squeezes the far end short.
[Design Omission] No flow limiting was provided and no balance valve was fitted, so the flow ran oversized.

Corrective Solution

1) Provide a flow-limiting valve on the near end (fit a flow-limiting or balance valve so the near-end flow is ≤110% of design), because the low near-end resistance robbed flow and pushed it above >120%, squeezing the far end, thereby distributing evenly by limiting the flow;
2) Verify the near-end resistance (measure the impedance and find it undersized), because a small resistance means oversized flow and verification reveals it, thereby locating the problem;
3) Add an orifice plate to limit the flow (fit a plate sized so the near-end pressure loss matches the surplus pressure), because an oversized flow biases the distribution and the plate limits it, thereby distributing the flow evenly by the orifice;
4) Equalize the resistance of the loops (adjust the balance valves so each loop's surplus pressure matches), because a difference makes the near end overshoot even more and equalizing balances it, thereby equalizing the resistance;
5) Check the flow (monitor the near-end flow, alarm above 115% of design), because a gradual increase starves the far end further and early detection helps, thereby monitoring the flow;
6) Run a water test (commission jointly and record the near-end and far-end flows), because the omitted test let the bias go unnoticed and the operation ran abnormally, thereby proving even distribution;
7) Control the total pressure (keep the total pressure steady against fluctuation), because off-design conditions worsen the near-end overshoot and steadiness preserves it, thereby stabilizing the pressure;
8) Write the flow limiting and resistance calibration into the calculation report, because the omitted limiting was the root cause of the near-end problem and the report enforces it, keeping the near end from robbing flow.

Checklist

Reference

GB/T 20801.3-2020 Design code for industrial metallic piping