Knowledge Base › Fluid Systems Error Case › Insufficient Flow in the Most Unfavorable Loop

Insufficient Flow in the Most Unfavorable Loop

E44-762 · Uneven Flow Distribution · Most Unfavorable Loop · ★★

Problem Description

The most unfavorable loop's flow was below <90% of design, far end starved

Root Cause

[Mechanism] The resistance of the most unfavorable loop is too high.
[Calculation] The high loop resistance drops that loop's flow below <90% of design and leaves the far end with insufficient differential pressure.
[Design Omission] The pipe diameter was not enlarged and nothing was verified, so the flow fell short.

Corrective Solution

1) Enlarge the pipe diameter of the most unfavorable loop (go up one size to cut that loop's impedance by 30%), because the original undersized pipe raised the loop resistance, dropped its flow below <90%, and starved the far end, thereby lowering the resistance and raising the flow by enlarging the diameter;
2) Verify the resistance of the most unfavorable loop (measure and find the Δp above the design value), because a high resistance starves the flow and verification reveals it, thereby locating the problem by measurement;
3) Provide booster make-up (add a small pump at that loop's far end or raise the pump head by 0.05MPa), because the low-end pressure is insufficient and make-up restores it, thereby preserving the flow by boosting the pressure;
4) Equalize the resistance of the loops (adjust the balance valves so each loop's surplus pressure matches), because a difference starves the unfavorable loop further and equalizing balances it, thereby distributing the flow evenly by equalizing resistance;
5) Check the flow (monitor the far-end flow, alarm below 90% of design), because gradual shortfall starves the far end first and early detection helps, thereby monitoring the flow;
6) Run a water test (commission the whole system and record the most unfavorable loop's flow), because the omitted test let the shortfall go unnoticed and the operation ran abnormally, thereby proving the flow meets target;
7) Control the total pressure (keep the pump outlet pressure steady against fluctuation), because off-design conditions starve the unfavorable loop further and steadiness preserves it, thereby stabilizing the pressure;
8) Write the diameter enlargement and resistance calibration into the calculation report, because the omitted enlargement was the root cause of the unfavorable loop and the report enforces it, giving the loop enough flow.

Checklist

Reference

GB/T 20801.3-2020 Design code for industrial metallic piping

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »