Dynamic Flow Surge

E44-768 · Uneven Flow Distribution · Dynamic Piping · ★★

Problem Description

Start-stop surge, flow transient >30%, pipe vibration

Root Cause

[Mechanism] A flow transient produces water hammer or surge.
[Calculation] A rate of change >30%/s makes the Δp rise suddenly and vibrates the pipe, biasing the flow.
[Design Omission] Startup was not slowed and no buffer was provided, so surge occurred.

Corrective Solution

1) Add a buffer tank to absorb the surge (volume sized for the transient flow × a damping time ≥30s), because the original rate of change >30%/s made the Δp rise suddenly and vibrated the pipe, biasing the flow, thereby absorbing the energy and steadying the flow;
2) Provide soft start and soft stop (valve rate ≤5%/s, staggered by time delay), because an abrupt change causes surge and a soft one reduces it, thereby steadying the flow;
3) Add an overflow relief against surge (safety valve set at 1.1 times, relieve on exceedance), because surge raises the pressure and relief lowers it, thereby protecting the pipe;
4) Limit the rate of change (raise the pump frequency at ≤10%/s), because an abrupt change causes surge and rate limiting steadies it, thereby steadying by limiting the rate;
5) Verify the pipe diameter against the change (size it so the transient velocity is ≤3m/s), because a small pipe surges harder and a large one soothes it, thereby reducing the surge by verifying the diameter;
6) Check for surge (monitor the pressure transient, alarm above Δp >0.3MPa), because gradual surging fatigues the pipe and early detection helps, thereby monitoring for surge;
7) Control the start-stop sequence (stagger multiple pumps by ≥10s), because starting together superposes the surge and staggering disperses it, thereby clipping the peak by sequence control;
8) Write the buffering and rate limiting into the specification, because the omitted buffering was the root cause of the surge and the specification enforces it, suppressing the surge.

Checklist

Reference

GB/T 20801.3-2020 Design code for industrial metallic piping