E44-031 · Level Control Failure · Magnetic Flap Level Gauge on Tank · ★★
A stuck float made the displayed level a false high of 0.3m, causing overflow and product loss twice a month
[Sticking] Material attaching to the guide tube jams the float, so the indication lags.
[Overflow] The false level keeps the feed running, so the tank overfills and overflows.
[Design Omission] No dual level-gauge comparison was provided and nothing was cleaned periodically, so the false level caused the overflow.
1) Provide dual level gauges (radar + magnetic flap) for comparison, because sticking of a single gauge gives a false high of 0.3m and causes overflow and product loss, while the two gauges cross-check and expose the false reading;
2) Clean the guide tube at intervals against sticking, because attachment jams the float and delays the indication, so cleaning keeps it free;
3) Select a sticking-resistant float structure, because it reduces attachment and jamming, thereby improving reliability;
4) Interlock a high level to stop the feed, because a genuinely high level stops the feed and prevents overfill and overflow, thereby protecting hard;
5) Verify the display and the remote reading in step, because they get out of step and cause misjudgment, thereby keeping them synchronized and accurate;
6) Provide overflow collection and alarm, because overflow and product loss cause losses and collection makes them controllable and alarmable;
7) Calibrate the level zero periodically, because zero drift biases the reading and calibration corrects it, thereby calibrating;
8) Include dual-gauge comparison in level management, because the single gauge was the root cause of the false level and management must use two gauges.
HG/T 21550-2013 Magnetic flap level gauges