E44-032 · Level Control Failure · Intermediate Tank Level · ★★
A fixed-speed pump with level controlled by an outlet valve oscillated ±0.4m, making the pump start-stop frequently, 15 times a month
[Control Fighting] The pump runs at a flow far above the outlet draw, so the valve throttles hard and the level swings widely.
[Limit Cycle] Improper gain in the control loop produces a limit-cycle oscillation.
[Design Omission] No pump variable-speed control was used and no PID tuning was done, so the competing controls oscillated.
1) Convert the pump to variable-speed control that sets flow by level, because a fixed-speed pump runs far above the outlet draw and hard valve throttling swings the level ±0.4m, thereby letting the flow follow the level;
2) Tune the PID parameters to eliminate the oscillation, because improper gain produces the limit cycle and tuning steadies the loop, thereby steadying the response;
3) Provide cascade control of level and flow, because cascade resists outlet disturbances and steadies the level, thereby steadying both loops;
4) Make the outlet valve follow rather than throttle hard, because following reduces throttling and flattens the level, thereby keeping the valve from swinging hard;
5) Provide a dead band against frequent start-stop, because frequent start-stop damages the equipment 15 times a month, and the dead band suppresses it, thereby suppressing the starts;
6) Provide high and low level alarms, because exceeding the limits causes overflow or supply loss and the alarms warn of it, thereby warning early;
7) Prove on trial run that the level fluctuation is ≤±0.1m (was ±0.4m), because a small fluctuation means steadiness, thereby accepting the installation;
8) Include the control scheme in the instrumentation design, because the omitted variable-speed control and tuning were the root cause of the oscillation and the design must include them.
GB/T 20819-2018 Process control — System evaluation