Knowledge Base › Fluid Systems Error Case › Radar Level Gauge Interference

Radar Level Gauge Interference

E44-614 · Level Control Failure · Radar Level Gauge · ★★

Problem Description

Reading jumps, interference

Root Cause

[Mechanism] Interference corrupts the wave reflection.
[Calculation] Interference makes the reading jump.
[Design Omission] No shielding, no frequency selection, and no adjustment were provided, so interference occurs.

Corrective Solution

1) Add a shield against interference (304 stainless mesh shield, shielding effectiveness ≥30dB), because the original radar (26GHz) picked up variable-frequency interference from the agitator motor, which lowered the echo signal-to-noise ratio and made the reading jump ±0.3m, and shielding blocks the space coupling, thereby reducing interference and steadying the reading;
2) Choose a low frequency to avoid interference (change from 26GHz to 6GHz, longer wavelength penetrates interference), because a high frequency is sensitive to side lobes from nearby metal while a low one has smaller side lobes, thereby avoiding near-field interference;
3) Adjust the transmit power and threshold (raise power to 80% of rated, set the echo threshold to noise floor +6dB), because a weak echo drowns in noise and raising the power and threshold distinguishes the true echo, thereby resisting misjudgment;
4) Mount it far from the agitator (antenna ≥1.5m from the agitator shaft), because the vortex close to the agitator disturbs the interface and mounting farther reduces it, thereby steadying the measurement;
5) Filter the jumping points (median filter plus rate limit ≤0.1m/s), because occasional spikes cause the jumps and filtering suppresses them, thereby smoothing the signal;
6) Calibrate the empty-tank zero (zero with an empty tank, error ≤1mm), because interference causes zero drift and zero calibration corrects it, thereby keeping the datum accurate;
7) Check for reading jumps at intervals (log the daily jump count), because growing interference increases the jumps and trending catches it early, thereby allowing timely shielding;
8) Write the shielding and frequency selection into the specification (mount the unit 3m clear of variable-frequency equipment), because the omitted shielding was the root cause of the interference and freezing it into the specification enforces design review.