Foam Error on Ultrasonic Level Transmitter

E44-615 · Level Control Failure · Ultrasonic Level Transmitter · ★★

Problem Description

Foam, false high reading

Root Cause

[Mechanism] Foam absorbs the sound wave and the reading runs high.
[Calculation] The foam drives the reading high.
[Design Omission] No foam avoidance, no frequency selection, and no compensation were provided, so the foam affects the reading.

Corrective Solution

1) Switch to guided-wave radar to avoid the foam (radar antenna inside a stilling pipe, measuring the true interface rather than the foam top), because the original ultrasonic (40kHz) wave was absorbed and scattered by the surface foam (0.3m thick, 90% gas), the echo returned from the foam top and inflated the reading by 0.3m, while guided-wave radar measures the liquid interface along the probe, thereby avoiding the foam and reading the true level;
2) Choose a low frequency to penetrate the foam (change from 40kHz to 10kHz, longer wavelength penetrates the foam), because a high frequency attenuates right at the foam while a low one penetrates to the liquid surface, thereby reducing the foam-induced high reading;
3) Add antifoam to reduce the foam (spray antifoam agent, foam height <50mm), because thick foam increases the error and defoaming lowers the height, thereby reducing the error;
4) Raise the transducer away from the foam (antenna ≥0.5m above the liquid surface, clear of foam splashing), because when close the wave hits the foam first and a higher position measures the liquid surface, thereby avoiding the error;
5) Apply temperature compensation to the reading (correct sound velocity for media temperature ±2m/s), because temperature change shifts the sound velocity and temperature compensation corrects it, thereby steadying the reading;
6) Calibrate the empty-span zero (calibrate with an empty tank, error ≤1mm), because foam causes zero drift and zero calibration corrects it, thereby keeping the datum accurate;
7) Check the foam condition at intervals (log the foam-height trend), because gradual thickening increases the error and inspection catches it early, thereby allowing timely re-selection;
8) Write the foam-avoidance selection into the specification (for foaming duty, no ultrasonic — use radar), because the omitted foam-avoidance selection was the root cause and freezing it into the specification enforces design review.

Checklist

Reference

GB/T 25922-2010 Radar level meters