E44-623 · Level Control Failure · Level PID · ★★
Oscillation, overshoot
[Mechanism] Poor PID tuning makes the loop oscillate.
[Calculation] Poor tuning produces 20% overshoot.
[Design Omission] The loop was not tuned, no auto-tuning was used, and no test was run, so the tuning is poor.
1) Re-tune the PID parameters (widen the proportional band PB from too narrow to 60%, integral Ti=20s, derivative Td=5s), because the original PB was too small (20%), which made the loop oscillate with 20% overshoot, and widening PB damps the oscillation, thereby steadying control and reducing overshoot;
2) Use auto-tuning to find the optimum (step-response auto-tuning), because manual tuning rarely reaches the optimum and auto-tuning sweeps the parameters to find the critical gain, thereby approaching the optimum;
3) Reduce the proportional gain for stability (cut it to 60% of the original), because high gain oscillates and reducing it steadies the loop, thereby damping the oscillation;
4) Add derivative action to suppress overshoot (derivative time Td=5s), because the overshoot comes from lag and derivative action anticipates it, thereby reducing overshoot;
5) Limit the output slew rate (≤5%/s), because abrupt output movement oscillates and a smooth output steadies the loop, thereby damping the oscillation;
6) Run a step test (apply a ±10% setpoint step and observe the response), because the absence of testing caused the poor tuning and the test verifies it, thereby confirming stability;
7) Check stability at intervals (log the overshoot and oscillation period), because gradual oscillation means poor tuning and trending catches it early, thereby prompting re-tuning;
8) Write the tuning and auto-tuning into the control card, because the missing tuning was the root cause and freezing it into the control card enforces control.
GB/T 17214 Industrial-process measurement and control