E44-622 · Level Control Failure · Level Control Valve · ★★
Stuck valve, level overshoot
[Mechanism] A stuck valve defeats the level control.
[Calculation] The sticking drives the level past the setpoint.
[Design Omission] The valve was not cleared, no fouling-resistant valve was selected, and it was not inspected, so it stuck.
1) Clean the valve to remove the sticking (strip the valve and clear the body, free travel clearance ≥0.5mm), because scale or particles (>0.5mm) in the valve body jammed the stem and the level ran away past the setpoint (e.g., by 5%), and cleaning restores movement, thereby restoring control;
2) Replace it with a sticking-resistant valve (eccentric rotary plug valve or metal-seated ball valve, suitable for solids), because a stuck valve loses control and a sticking-resistant valve tolerates fouling, thereby resisting sticking;
3) Add purging against plugging and sticking (purge the stem with instrument air at 0.1MPa), because plugging sticks the valve and purging clears it, thereby preventing sticking;
4) Verify the stroke to prevent sticking (calibrate the positioner stroke, dead band ≤1%), because a mis-adjusted stroke sticks and calibration corrects it, thereby keeping the stroke accurate;
5) Control media cleanliness (suspended solids <0.1%), because dirt sticks the valve and cleanliness lowers the load, thereby extending the cleaning interval;
6) Check for sticking (manually check stem freedom each month), because gradual sticking loses control and inspection catches it early, thereby allowing preemptive cleaning;
7) Limit the stroke rate for smooth motion (rate ≤10%/s), because abrupt movement sticks the valve and smooth motion steadies it, thereby preventing sticking;
8) Write the cleaning and valve replacement into the maintenance card, because the missed cleaning was the root cause of the sticking and freezing it into the maintenance card enforces maintenance.
GB/T 12224-2015 Steel valves