E44-629 · Level Control Failure · Transmitter · ★★
Wrong range, reading offset
[Mechanism] A wrong range offsets the reading.
[Calculation] The calibration error causes the deviation.
[Design Omission] The range was not set, not verified and not inspected — so it was wrong.
1) Reset the range to match (the range equals the pressure corresponding to the tank height, e.g. 0-10kPa for 0-5m): because the original wrong range (e.g. 0-16kPa) made a full tank read only 62%, setting the range correctly restores accuracy;
2) Verify the range against the tank height (per the drawing, the upper limit = liquid column height × ρg): because a mismatch offsets it and verifying the range corrects it, they match;
3) Calibrate the full span (full-tank calibration, error ≤0.1%FS): because an offset requires calibration and calibration verifies it, it is confirmed;
4) Display the range for confirmation (range and units on the screen): because hiding it hides the error and displaying it allows cross-checking, errors are prevented;
5) Select a suitably ranged transmitter (turndown ≥10:1): because a wrong range offsets it and a suitable range is accurate, the reading is steady;
6) Check for reading offset (compare with the scale daily): because gradual offset causes error and checking verifies it, calibration is timely;
7) Restrict change access (a two-level password to change the range): because arbitrary changes cause error and access control prevents it, misoperation is prevented;
8) Write the range setting and verification into the maintenance card: the original lack of setting was the root cause of the error, so the card locks it in and maintenance governs it.
GB/T 17614.1-2008 Transmitters for use in industrial-process control systems