Knowledge Base › Fluid Systems Error Case › Wrong Level Interlock Setting

Wrong Level Interlock Setting

E44-634 · Level Control Failure · Interlock setpoint · ★★★

Problem Description

Wrong setting, did not act

Root Cause

[Mechanism] A wrong setting prevents it from acting.
[Calculation] The error prevents the trip.
[Design Omission] The setting was not verified, not tested and not access-controlled — so it was wrong.

Corrective Solution

1) Verify and reset the interlock value (set per the HAZOP, error ≤1mm): because the original interlock was set incorrectly (e.g. the high interlock set 100mm low) and the level exceeded the limit without tripping, verifying the value corrects it so it trips as soon as the limit is exceeded;
2) Run an interlock test (simulate rising and falling levels to verify the trip): because without a test the failure is unverified and the test proves it, the trip is confirmed;
3) Add access control against misoperation (a two-level password): because changing it at will causes the error and access control prevents it, misoperation is prevented;
4) Display the interlock value for confirmation (value plus units on the screen): because hiding it hides the error and displaying it allows cross-checking, errors are prevented;
5) Verify the measured value against the interlock (compare the measured value with the setting): because a deviation causes the error and comparison verifies it, it is confirmed;
6) Check the interlock condition (check daily): because gradual error causes the failure and checking gives early warning, errors are prevented;
7) Require two signatures to confirm the value (changing the value needs two signatures): because a single person can err and two signatures cross-check, misoperation is prevented;
8) Write the value verification and interlock testing into the control card: the original lack of verification was the root cause of the error, so the card locks it in and control governs it.

Checklist

Reference

GB/T 17214 Industrial-process measurement and control

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »