E44-637 · Level Control Failure · Agitation · ★★
Swinging makes the measurement unsteady
[Mechanism] Agitation makes the surface swing, so the measurement is unsteady.
[Calculation] The swinging causes fluctuation.
[Design Omission] The flow was not steadied, not filtered and not baffled — so it swung.
1) Lower the agitator speed to steady the liquid (speed down to 80% of the original, smaller vortex): because the original high speed (e.g. 120rpm) rolled a vortex that swung the surface ±0.1m, lowering the speed reduces the vortex so the surface steadies and the reading is smooth;
2) Add a filter algorithm to smooth it (moving-average window 10s): because swinging makes it jump and filtering suppresses the spikes, the signal is smooth;
3) Choose a guided-wave measuring point away from the vortex (probe 0.3m off the vortex center): because the vortex swings it and avoiding the vortex steadies it, the measurement is steady;
4) Provide a flow-stabilizing baffle (baffle height 0.3× the diameter): because the vortex swings it and the baffle breaks up the vortex, the swinging is reduced;
5) Calibrate against the average reading (use the mean rather than the instantaneous value): because swinging offsets it and the mean is true, it is confirmed;
6) Check the swing amplitude (measure the peak-to-peak fluctuation weekly): because gradual swinging causes error and checking gives early warning, the speed is reduced in time;
7) Control the level margin against overflow (operating level ≤85%): because swinging can overflow and leaving a margin protects, overflow is prevented;
8) Write the speed reduction and filtering into the control card: the original lack of steadying was the root cause of the swinging, so the card locks it in and control governs it.
GB/T 17214 Industrial-process measurement and control