E44-638 · Level Control Failure · Steam condensate · ★★
Condensate causes fluctuation
[Mechanism] Condensate changes the density, causing the fluctuation.
[Calculation] Condensation causes the fluctuation.
[Design Omission] The condensate was not drained, not stabilized and not replenished — so it condensed.
1) Provide a condensate drain valve and drain on a schedule (once per shift): because the original steam condensate (yield about 0.5kg/min) collected in the impulse line and the liquid column fluctuated, making the reading swing ±0.1m, draining clears it so the zero is steady;
2) Insulate against condensation (insulation 50mm thick): because cold condenses it and insulation reduces condensation, the reading is steady;
3) Replenish the condensate head (the seal liquid head kept constant ±1mm): because a head difference causes fluctuation and replenishing levels it, the reading is steady;
4) Select a temperature-resistant instrument (transmitter rated to ≤120℃): because temperature changes cause fluctuation and temperature resistance steadies it, the measurement is steady;
5) Calibrate against the mean of the fluctuation (use the average): because swinging offsets it and the average is true, it is confirmed;
6) Check for condensation (inspect for accumulated liquid weekly): because gradual condensation increases the fluctuation and checking gives early warning, draining is timely;
7) Control the pressure to steady the condensation (operating pressure steady to ±0.02MPa): because changing conditions condense it and steady pressure reduces it, the reading is steady;
8) Write the condensate draining and insulation into the maintenance card: the original lack of draining was the root cause of the condensation, so the card locks it in and maintenance governs it.
GB/T 17614.1-2008 Transmitters for use in industrial-process control systems