E44-643 · Level Control Failure · Condensate · ★★
Loss, offset, changed differential
[Mechanism] Losing the condensate offsets the differential pressure.
[Calculation] The loss causes the offset.
[Design Omission] The condensate was not replenished, not sealed and not inspected — so it was lost.
1) Replenish the condensate to restore the head (fill to the design mark ±1mm): because the original condensate evaporated and was lost (level down 5mm), making the high- and low-pressure legs unequal and offsetting the differential pressure (0.1m off), replenishing levels them so the reading returns to accuracy;
2) Seal the liquid against evaporation (seal fluid density 1.2, closed filling): because evaporation loses it and sealing cuts it, the liquid level is steady;
3) Calibrate zero and full (empty / full calibration, error ≤0.5%): because an offset requires calibration and calibration corrects it, it is confirmed;
4) Select a stable seal fluid (silicone oil, low volatility): because changing conditions lose it and a stable fluid holds, it is steady;
5) Control the temperature against evaporation (trace heating plus insulation holding ΔT <5℃): because heat loses it and temperature control reduces evaporation, the loss is prevented;
6) Check for loss (inspect the liquid mark weekly): because gradual loss increases the offset and checking gives early warning, it is replenished in time;
7) Check and replenish periodically (inspect and top up monthly): because it is lost gradually and replenishing restores it, the level is maintained;
8) Write the replenishment and sealing into the maintenance card: the original lack of replenishment was the root cause of the loss, so the card locks it in and maintenance governs it.
GB/T 17614.1-2008 Transmitters for use in industrial-process control systems