E44-642 · Level Control Failure · Heat tracing · ★★
Frozen, blocked, reading lost
[Mechanism] Insufficient heat tracing freezes and blocks it.
[Calculation] Freezing blocks it and loses the reading.
[Design Omission] The heat tracing was inadequate, the temperature was not controlled and no checks were made — so it froze.
1) Provide adequate heat tracing against freezing (tracing power ≥1.2× the design, wall temperature ≥5℃): because the original inadequate tracing let the medium in the impulse line (Φ10) freeze and block at -10℃ and lose the reading, adequate tracing keeps it warm so the line clears and the measurement resumes;
2) Hold the tracing temperature ≥5℃ (self-adjusting to ±2℃): because low temperature freezes it and temperature control prevents it, freezing is avoided;
3) Add self-adjusting temperature control (electric heat-tracing tape plus a thermostat): because changing conditions freeze it and self-adjustment steadies it, the temperature is steady;
4) Keep the tracing even (wrap spacing ≤150mm): because an uneven wrap freezes and even tracing evens it, it does not freeze;
5) Check for freezing (inspect the pipe temperature weekly): because gradual freezing loses the reading and checking gives early warning, tracing is applied early;
6) Drain residual liquid against freezing (drain fully when out of service): because trapped liquid freezes and draining prevents it, freezing is avoided;
7) Select a freeze-resistant instrument (low-temperature transmitter): because freezing loses the reading and freeze resistance steadies it, the measurement is steady;
8) Write the adequate tracing and temperature control into the maintenance card: the original lack of tracing was the root cause of the freezing, so the card locks it in and maintenance governs it.
GB/T 50235-2010 Industrial metallic piping construction