E44-651 · Level Control Failure · Viscous liquid · ★★
Wall clinging, offset, low reading
[Mechanism] The viscous liquid clings to the wall and offsets the reading.
[Calculation] The clinging causes the offset.
[Design Omission] No heating, no instrument selection and no cleaning were provided — so the liquid clung.
1) Add heat tracing to cut viscosity and prevent clinging (steam tracing ≥ the medium's pour point + 10℃): because the original viscous liquid (viscosity >2000cP) clung to the wall, reducing the effective cross-section and reading low (0.15m off), heating lowers the viscosity and reduces the clinging so the reading returns to the true value;
2) Select a non-contact measurement (non-contact radar or ultrasonic): because wall clinging offsets the reading and the non-contact method is unaffected by it, the measurement is accurate;
3) Clean the wall of the viscous film periodically (high-pressure water wash every shift): because accumulation clings and cleaning restores it, the reading is maintained;
4) Polish the probe to a smooth finish (Ra0.4μm): because a rough surface clings easily and a smooth one reduces adhesion, clinging drops;
5) Control the temperature against condensation and sticking (insulation holding ΔT <5℃): because cold causes clinging and temperature control reduces it, clinging is prevented;
6) Calibrate the full level (full-tank calibration): because an offset requires calibration and calibration corrects it, the reading is confirmed;
7) Inspect for clinging (check the wall thickness weekly): because gradual clinging increases the offset and checking gives early warning, cleaning is timely;
8) Write the heat tracing and instrument selection into the specification: the original lack of heating was the root cause of the clinging, so the spec locks it in and specification governs it.
GB/T 25922-2010 Level meters