Knowledge Base › Fluid Systems Error Case › Condensation on a Cooled Vessel Causing a False Level Reading

Condensation on a Cooled Vessel Causing a False Level Reading

E44-655 · Level Control Failure · Cooled tank · ★★

Problem Description

Condensation, falsely high reading, error

Root Cause

[Mechanism] Condensation makes the reading falsely high.
[Calculation] The condensation causes the error.
[Design Omission] No insulation, no separation and no compensation were provided — so condensation formed.

Corrective Solution

1) Add insulation against condensation (a 50mm insulating layer, wall temperature > the dew point): because the original cooled wall was below the dew point (e.g. wall 8℃ < dew point 12℃), condensation formed and the reading was falsely high by 0.1m; the insulation raises the wall above the dew point so no condensation forms and the reading returns to the true value;
2) Provide an isolating jacket against condensation (a dry-air gap): because cold causes condensation and the jacket isolates it, condensation is prevented;
3) Apply dew-point compensation (correct by humidity): because condensation causes the error and compensation corrects it, the false-high reading is reduced;
4) Select a non-contact measurement (non-contact radar): because condensation causes the error and the non-contact method is unaffected by it, the measurement is accurate;
5) Hold the wall temperature above the dew point (trace heating to wall > dew point + 2℃): because low temperature causes condensation and temperature control prevents it, condensation is avoided;
6) Verify the reading (compare with a gauge): because a deviation requires calibration and calibration corrects it, the reading is confirmed;
7) Inspect for condensation (check the wall for water weekly): because gradual condensation increases the offset and checking gives early warning, insulation is timely;
8) Write the insulation and compensation into the specification: the original lack of insulation was the root cause of the condensation, so the spec locks it in and specification governs it.

Checklist

Reference

GB/T 25922-2010 Level meters