E44-658 · Level Control Failure · Guided-wave pipe · ★★
Blocked, signal lost, reading frozen
[Mechanism] A blocked guide pipe loses the signal.
[Calculation] The blockage causes the loss.
[Design Omission] The pipe was not cleaned, not purged and not inspected — so it blocked.
1) Clean the guide pipe through (remove it and flush with high-pressure water): because the original scale blockage in the guide pipe killed the wave guidance and froze the reading with an offset (0.2m off), cleaning restores the measurement so the clear pipe reads correctly;
2) Provide back-purge against blockage (instrument air back-purge at 0.1MPa): because dirt blocks it and back-purge clears it, blockage is prevented;
3) Add blowdown to clear blockage (drain every shift): because accumulation blocks it and blowdown clears it, the pipe is maintained;
4) Select a larger guide bore (change Φ10 to Φ15): because a narrow bore blocks and a larger bore reduces deposits, blockage drops;
5) Trace-heat against condensate blockage (≥80℃): because condensation blocks it and tracing prevents it, condensation is avoided;
6) Verify the zero (compare with a gauge): because a loss requires calibration and calibration corrects it, the zero is confirmed;
7) Inspect for blockage periodically (rod the pipe through weekly): because blockage develops gradually and checking gives early warning, signal loss is prevented;
8) Write the pipe cleaning and back-purge into the maintenance card: the original failure to clean was the root cause of the blockage, so the card locks it in and maintenance governs it.
GB/T 25922-2010 Level meters