Uncompensated Thermal Expansion - Large Displacement

E44-788 · Piping Supports and Thermal Expansion · Thermal expansion · ★★★

Problem Description

No compensation, displacement >80mm, stress above allowable

Root Cause

[Mechanism] With no expansion joint, the thermal growth has no outlet.
[Calculation] The temperature rise drives the straight-run displacement >80mm and the stress 2× the allowable.
[Design Omission] Neither compensation was provided nor the displacement calculated — so compensation must be added.

Corrective Solution

1) Install an expansion joint to absorb the growth (axial compensation ≥ the calculated displacement + a 10% margin): because the original lack of compensation drove the straight-run displacement >80mm and the stress 2× the allowable, compensation reduces the displacement;
2) Calculate the thermal displacement (ΔL=αLΔT, checked at each point): because the lack of calculation caused the excess and calculating reveals it, the displacement is calculated and located;
3) Verify the compensation capacity (select ≥ 1.1× the displacement): because too small an excess and verifying makes it sufficient, the capacity is verified;
4) Add a π-bend for compensation (natural-compensation arm length per calculation): because a straight run over-travels and a bend absorbs, a bend is added to absorb the growth;
5) Monitor the displacement (displacement markers, alarm > the design value): because gradual growth raises the stress and early awareness helps, the displacement is monitored;
6) Run a hot test (raise the temperature and record the displacement at each point against the calculation): because the original lack of testing left the excess undiscovered and the test reveals the true displacement, the hot test verifies it;
7) Control the temperature to prevent a steep ramp (≤50℃/h): because a steep ramp over-travels and a slow one keeps it under control, the temperature is controlled;
8) Write the compensation and displacement calculation into the calculation sheet: the original lack of compensation was the root cause of the growth, so calculation controls the design and the stress is acceptable.