Spring Can Jamming

E44-797 · Piping Supports and Thermal Expansion · Spring Can · ★★

Problem Description

Spring can jammed, no follow-up movement, displacement blocked

Root Cause

[Mechanism] Rust / debris inside the can makes the spring stick and stop following up.
[Calculation] The jam blocks the displacement and raises the thermal stress >30MPa.
[Design Omission] Neither lubrication nor cleaning was provided — so it must be lubricated.

Corrective Solution

1) Clean the spring can and grease it (disassemble, remove rust, apply grease, keep it sliding): because the original rust jam blocked the displacement and raised the stress >30MPa, cleaning and lubrication keep it moving;
2) Check the internal clearance (guide clearance ≥1mm to prevent jamming): because too tight jams and the check keeps it free, the clearance is checked;
3) Replace the jammed spring (replace on deformation / rusted breakage): because a jam loses the function and replacement restores it, the spring is replaced;
4) Apply an anti-corrosion layer (galvanize / stainless steel inside the can): because rust jams and rust prevention preserves it, corrosion protection is applied;
5) Monitor the jam (displacement-mark monitoring, alarm on jamming): because progressive jamming raises the stress and early awareness helps, jamming is monitored;
6) Perform a follow-up test (heat and cool while recording the can displacement): because the original lack of testing left the failure undiscovered, the test reveals the follow-up ability, so follow-up is tested;
7) Keep the load stable (distribute the pipe weight evenly to cut the per-can load): because a changing duty jams and even distribution stabilizes it, the load is stabilized;
8) Write the cleaning, lubrication and clearance check into the maintenance card: the original lack of lubrication was the root cause of the jamming, so maintenance controls the work and the follow-up stays free.

Checklist

Reference

GB/T 17116.1-2018 Pipe supports and hangers