Knowledge Base › Fluid Systems Error Case › Seismic Support Failure

Seismic Support Failure

E44-839 · Piping Supports and Thermal Expansion · DN500 Gas-Pipe Seismic Supports · ★★★

Problem Description

With seismic design intensity 8 the original ordinary supports were not seismic; after the quake the supports fell off and the pipe displaced 80mm

Root Cause

[Mechanism] The horizontal seismic acceleration produces an inertial force in the piping; the ordinary supports carry only vertical load, with no horizontal shear resistance or pull-out anchorage, so the anchor bolts are pulled out.
[Calculation] Horizontal seismic force F=α·G=0.16× pipe weight (with contents) ≈28kN, exceeding the ordinary hanger lateral capacity of 5kN and the anchor pull-out capacity of 8kN; the displacement Δ=F/k>80mm.
[Design Omission] No seismic supports were provided per GB50981, no diagonal bracing for shear, and the anchorage was not checked for pull-out.

Corrective Solution

1) Provide seismic supports (per GB50981, lateral + longitudinal spacing ≤12m): because the original ordinary supports carried only vertical load and fell off in the quake, seismic supports hold the pipe;
2) Add diagonal bracing for shear (45° brace, each ≥30kN for horizontal load): because the lateral 28kN in the quake caused fall-off, the bracing resists shear;
3) Verify the seismic intensity (horizontal acceleration 0.16g for intensity 8): because under-designing fails, the check makes it sufficient;
4) Weld the anchorage securely (post-installed undercut anchors M12, pull-out ≥12kN, double nuts): because looseness drops it, welding holds it;
5) Inspect the seismic state (after a quake check the displacement and anchor tightness, alarm at displacement >50mm): because gradual failure brings pipe fall-off closer, early awareness helps;
6) Run a seismic test (shake-table simulation of intensity 8, recording displacement): because the original lack of testing hid the failure, the test reveals the displacement;
7) Use flexible connections (add metal hose at equipment nozzles to absorb seismic movement): because a rigid joint cracks the nozzle, flexibility relieves it;
8) Write the seismic supports, bracing and anchorage into the assembly card: the original lack of seismic resistance was the root cause, so fixing it closes the loop;

Checklist

Reference

GB/T 17116.1-2018 Pipe supports and hangers

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL