E44-147 · Throttling Noise and Vibration · Steam Trap Discharge Pipe · ★★
After the steam trap, high-speed flash steam is discharged directly, giving 98dB noise and loosening the support
[Direct Discharge] High-speed flash steam discharged directly generates noise.
[Vibration] The discharge pulsation excites vibration.
[Design Omission] Neither silencing nor reinforcement was provided — hence the noise and vibration.
1) Install a silencer on the pipe after the steam trap: because high-speed flash steam is discharged directly at 98dB, silencing cuts the dB;
2) Provide a diffuser at the discharge to slow and stabilize the flow: because direct discharge excites vibration, gradual expansion stabilizes it;
3) Densify and damp the supports to prevent loosening: because vibration loosens the supports, damping locks them;
4) Select a low-noise steam trap to prevent steam hammer: because steam hammer makes noise, a low-noise model is chosen;
5) Slope the drain pipe so it flows freely and does not accumulate: because accumulated water causes noise, a smooth slope helps;
6) Isolate the discharge from the building: because transmitted vibration disturbs occupants, isolation is used;
7) Measure noise ≤85dB at commissioning: the design requirement must be verified by measurement, confirming delivery;
8) Include silencing and reinforcement in the discharge design: the original direct discharge was the root cause of the noise and vibration, so it must be included in design.
GB/T 17213.1-2015 Industrial-process control valves