Knowledge Base › Fluid Systems Error Case › Valve Positioner Oscillation

Valve Positioner Oscillation

E44-855 · Throttling Noise and Vibration · Positioner · ★★

Problem Description

The high gain of the electro-pneumatic positioner made the valve stem dither ±3% and the control signal unstable

Root Cause

[Mechanism] The positioner gain is set too high, and the actuator and positioner form a positive-feedback self-excited oscillation.
[Calculation] Open-loop gain K=K_pos×K_act>1, self-excitation occurs at a 180° phase shift; the dither frequency rises as the gain rises.
[Design Omission] No gain tuning, no reduced response speed, no switch to an anti-vibration type.

Corrective Solution

1) Tune the positioner (lower the gain to open-loop K<1), since the original high gain made the stem dither ±3%, thus tuning steadies the position;
2) Verify the gain is moderate (adjust the proportional band to the stable region), since high dithers and verification keeps it safe, thus verifying the gain;
3) Reduce the response speed (increase the dead band to prevent high-frequency self-excitation), since too fast dithers and reducing steadies it, thus reducing speed;
4) Switch to an anti-vibration type (a digital positioner instead of analog), since weak dithers and the replacement is stable, thus switching the type;
5) Monitor the dither (measure the stem dither amplitude, alarm >±1%), since gradual dither approaches wear and early detection catches it, thus monitoring the dither;
6) Run a stability test (sweep frequency to find the self-excitation point), since the lack of testing left the dither undetected and the test reveals the threshold, thus testing stability;
7) Control the air supply steadily (purify and stabilize the air supply), since fluctuation dithers and steadying controls it, thus controlling the source;
8) Write the tuning and gain verification into the specification, since the original lack of tuning is the root cause of dither and locking it in closes the loop, thus controlling it in the spec.

Checklist

Reference

GB/T 17213.1-2015 Industrial-process control valves

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »