E44-040 · Siphoning and Backflow · High-level tank outlet pipe · ★★
A leaking check valve let siphon backflow occur after pump shutdown; the tank overflowed and flooded the pump room once
[Siphoning] The 6m elevation difference H produces backflow Q=A√(2gH), and the return flow overflows the tank.
[Backflow] Check-valve failure keeps the siphon running.
[Design Omission] No siphon break was provided (air valve), and the leaking check valve was not repaired, so the backflow overflowed the tank.
1) Repair the check valve promptly to restore anti-reverse flow, since the leaking check valve kept the siphon backflowing and flooded the pump room, thus repairing the valve stops the flow;
2) Install an air valve at the highest point to break the siphon, since breaking the vacuum interrupts the siphon and stops the backflow, thus breaking the siphon;
3) Fit a vacuum breaker on the outlet pipe, since it destroys the negative pressure and interrupts the siphon, thus providing a second safeguard;
4) Provide an overflow alarm and level limit on the tank, since overflow triggers the alarm and the level limit prevents it, thus making it controllable;
5) Add one-way backflow prevention at the low point, since a one-way check there blocks reverse flow, thus hard prevention;
6) Test the check-valve action periodically, since valve leakage is progressive and testing finds it early, thus scheduled testing;
7) Verify during commissioning that shutdown causes no backflow, since verification confirms it, thus acceptance;
8) Include siphon breaking in the piping design, since the original lack of siphon breaking is the root cause of backflow, thus the design must include it.
GB/T 20801-2020 Pressure piping code