Knowledge Base › Fluid Systems Error Case › Tank Overflow and Pump-Room Flooding from Siphon Backflow After Pump Shutdown

Tank Overflow and Pump-Room Flooding from Siphon Backflow After Pump Shutdown

E44-040 · Siphoning and Backflow · High-level tank outlet pipe · ★★

Problem Description

A leaking check valve let siphon backflow occur after pump shutdown; the tank overflowed and flooded the pump room once

Root Cause

[Siphoning] The 6m elevation difference H produces backflow Q=A√(2gH), and the return flow overflows the tank.
[Backflow] Check-valve failure keeps the siphon running.
[Design Omission] No siphon break was provided (air valve), and the leaking check valve was not repaired, so the backflow overflowed the tank.

Corrective Solution

1) Repair the check valve promptly to restore anti-reverse flow, since the leaking check valve kept the siphon backflowing and flooded the pump room, thus repairing the valve stops the flow;
2) Install an air valve at the highest point to break the siphon, since breaking the vacuum interrupts the siphon and stops the backflow, thus breaking the siphon;
3) Fit a vacuum breaker on the outlet pipe, since it destroys the negative pressure and interrupts the siphon, thus providing a second safeguard;
4) Provide an overflow alarm and level limit on the tank, since overflow triggers the alarm and the level limit prevents it, thus making it controllable;
5) Add one-way backflow prevention at the low point, since a one-way check there blocks reverse flow, thus hard prevention;
6) Test the check-valve action periodically, since valve leakage is progressive and testing finds it early, thus scheduled testing;
7) Verify during commissioning that shutdown causes no backflow, since verification confirms it, thus acceptance;
8) Include siphon breaking in the piping design, since the original lack of siphon breaking is the root cause of backflow, thus the design must include it.

Checklist

Reference

GB/T 20801-2020 Pressure piping code

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »