E44-192 · Siphon and Backflow · Workshop Floor Drain · ★★
The trap dries out with no water seal, and sewer odor flows back, giving the workshop a foul smell
[Dry-out] Loss of the water seal breaks the isolation.
[Backflow] Pressure fluctuation lets the odor return upward.
[Design Omission] No make-up water and no anti-dry-out provision, so backflow occurred.
1) Provide make-up water to the floor-drain trap to prevent dry-out, because a dry trap has no water seal and odor flows back, thereby keeping the seal by replenishment;
2) Use an anti-dry-out trap (deep seal/self-sealing), because it dries easily, thereby choosing a dry-out-resistant type;
3) Periodically check the water-seal depth is ≥50 mm, because it evaporates gradually, thereby checking on schedule;
4) Install a vent pipe in the sewer to balance the pressure, because pressure fluctuation causes backflow, thereby venting;
5) Provide double sealing for floor drains in the clean zone, because the requirement is high, thereby double sealing;
6) Monitor and alarm on odor, because backflow is detectable, thereby monitoring and alarming;
7) Commission and verify there is no odor backflow, because the design requires measurement, thereby confirming at delivery;
8) Include water-seal make-up in the drainage design, because the original lack of make-up is the root cause of the dry-out, thereby the design must include it.
GB/T 50015-2019 Code for Design of Building Water Supply and Drainage