Knowledge Base › Fluid Systems Error Case › Elevated Tank Overflow Pipe Without Siphon Break Causing Backflow Contamination

Elevated Tank Overflow Pipe Without Siphon Break Causing Backflow Contamination

E44-146 · Siphon and Backflow · Elevated Domestic Water Tank · ★★

Problem Description

The submerged overflow-pipe mouth forms a siphon, and sewage is drawn back, contaminating the clean-water tank

Root Cause

[Siphon] The submerged overflow-pipe mouth sustains a siphon.
[Contamination] The backflow mixes in sewage.
[Design Omission] No air gap/vacuum break, so backflow caused contamination.

Corrective Solution

1) Provide an air gap (≥2D) at the overflow-pipe mouth to break the siphon, because a submerged mouth keeps drawing backflow contamination, thereby the gap breaking the siphon;
2) Install a vacuum breaker at the highest point, because the siphon keeps flowing, thereby breaking the vacuum to stop the backflow;
3) Terminate the overflow pipe into the drain trench without submergence, because submergence causes a siphon, thereby leaving the outlet above water;
4) Provide a level alarm on the tank to prevent overflow, because overflow is hazardous, thereby alarming;
5) Isolate the clean-water and sewage systems, because mixing contaminates, thereby isolating;
6) Periodically check the overflow pipe is not submerged, because settling or alterations cause submergence, thereby checking periodically;
7) Commission and verify there is no backflow contamination, because the design requires measurement, thereby confirming at delivery;
8) Include the air gap in the water-supply design, because the original lack of a gap is the root cause of backflow, thereby the design must include it.

Checklist

Reference

GB/T 50015-2019 Code for Design of Building Water Supply and Drainage